Technical data

Datasheets.

Every storage system we offer, with the key technical data at a glance. You can save each datasheet as a PDF.

Discuss your project
Commercial & industrial

Aqua-E233

All-in-one cabinet for commercial and industrial sites: battery, inverter, cooling and fire protection pre-installed. Needs only about 1.4 m² of floor space.

233 kWhRated energy
110 kWRated power
≥ 7,000Cycle life
IP55Ingress protection

Battery

Rated energy233 kWh
Rated power110 kW
Cell typeLFP 3.2 V / 280 Ah
Battery configuration1P260S
Battery voltage range676–949 V DC

Grid side

AC nominal voltage400 V AC
AC voltage range340–460 V AC
Frequency50 ± 5 Hz
Current THD< 3 %

System

Efficiency≥ 87 % @ 0.5P
Cycle life≥ 7,000
CoolingLiquid cooling
Ingress protectionIP55
Operating temperature−30 to +55 °C (derating above 45 °C)
Relative humidity5–95 % RH, non-condensing
Max. altitude2,000 m
Dimensions (W × D × H)1,050 × 1,350 × 2,400 mm
Weight2,450 ± 50 kg
CommunicationEthernet, CAN, RS485, 4G optional

Safety

Corrosion classC3, C4 optional
Fire protectionAerosol suppression, smoke and heat detectors, horn strobe

Standards and grid codes

IEC 62619IEC 63056IEC 62477UN 38.3
Manufacturer data, 2026
Commercial & industrial

Aqua-E261

The most requested commercial unit: 261 kWh in one cabinet, freely combinable. Award winner at Solar Energy Expo Warsaw 2026.

261 kWhRated energy
125 kWRated power
≥ 7,000Cycle life
IP55Ingress protection

Battery

Rated energy261 kWh
Rated power125 kW
Cell typeLFP 3.2 V / 314 Ah
Battery configuration1P260S
Battery voltage range676–949 V DC

Grid side

AC nominal voltage400 V AC
AC voltage range340–460 V AC
Frequency50 ± 5 Hz
Current THD< 3 %

System

Efficiency≥ 87 % @ 0.5P
Cycle life≥ 7,000
CoolingLiquid cooling
Ingress protectionIP55
Operating temperature−30 to +55 °C (derating above 45 °C)
Relative humidity5–95 % RH, non-condensing
Max. altitude2,000 m
Noise≤ 70 dB
Dimensions (W × D × H)1,150 × 1,500 × 2,400 mm
Weight2,700 ± 50 kg
CommunicationEthernet, CAN, RS485, 4G

Safety

Corrosion classC3, C4 optional
Fire protectionAerosol suppression, smoke and heat detectors, horn strobe

Standards and grid codes

IEC 62619IEC 63056IEC 62040IEC 62477UN 38.3
Manufacturer data, 2026
Commercial & industrial

Aqua-X261

Commercial unit with built-in PV input (MPPT). Solar modules connect directly; with the optional transfer switch the site keeps running during a grid outage.

261 kWhRated energy
125 kWRated power
up to 2 × 60 kWPV input
< 20 msOn/off-grid switchover

Battery

Rated energy261 kWh
Rated power125 kW / 125 kVA
Cell typeLFP 3.2 V / 314 Ah
Battery configuration1P260S
Battery voltage range702–936 V DC
PV input60 kW or 2 × 60 kW, 4 or 8 MPPT, 150–672 V DC

Grid side

AC nominal voltage400 V AC
AC voltage range340–460 V AC
Frequency50 ± 5 Hz
Current THD< 3 %
On/off-grid switchover< 20 ms (with optional STS)

System

EfficiencyInverter up to 98.9 %
Cycle life≥ 7,000
CoolingLiquid and forced-air cooling
Ingress protectionIP55 battery, IP54 equipment
Operating temperature−30 to +55 °C (derating above 45 °C)
Dimensions (W × D × H)1,800 × 1,548 × 2,182 mm
Weight≤ 3,000 kg
CommunicationEthernet, RS485, 4G

Safety

Corrosion classC3, C4 optional
Fire protectionAerosol suppression, smoke and heat detectors, horn strobe; optional fire hose coupling and explosion vent panel

Standards and grid codes

IEC 62477-1IEC 62109-1/-2IEC 62619UN 38.3
Manufacturer data, 2026
Containerised utility storage

Aqua-C2.5 Mini

Utility storage in a 10-foot container with integrated inverter. Under 23 tonnes, so easy to transport and to install where space is tight.

2,089 / 2,508 kWhRated energy
500 / 625 kVARated power
IP66Ingress protection
≤ 23 / 25 tWeight

Battery

Rated energy2,089 kWh / 2,508 kWh
Rated power500 kVA / 625 kVA (4 hours)
Cell typeLFP 3.2 V / 314 Ah
Battery configuration5P416S / 6P416S
Battery voltage range1,081.6–1,497.6 V DC
Nominal battery voltage1,331.2 V

Grid side

AC nominal voltage550 V AC
AC voltage range495–605 V AC
Frequency50 / 60 Hz
Current THD< 3 %
Power factor≥ 0.99 (−1 … +1)

System

CoolingLiquid cooling
Ingress protectionIP66
Operating temperature−30 to +50 °C
Relative humidity≤ 100 % RH, non-condensing
Max. altitude3,000 m
Noise≤ 75 dB (1 m, 35 °C)
Dimensions (W × D × H)3,126 × 2,438 × 2,896 mm
Weight≤ 23,000 kg / ≤ 25,000 kg
CommunicationEthernet
ProtocolsModbus TCP, IEC 104, IEC 61850

Safety

Corrosion classC4, C5 optional
Seismic ratingIEEE 693 high level
Fire protectionFire alarm panel, smoke, heat and gas detectors, ventilation to NFPA 69, dry-pipe sprinklers, aerosol, deflagration venting optional

Standards and grid codes

IEC 62933-5-2IEC 61000IEC 62619IEC 63056IEC 62477-1
Manufacturer data, 2026
Containerised utility storage

Aqua-C2.5

The proven 5 MWh container, in service in Europe in Bulgaria, Bosnia and Herzegovina, North Macedonia and France, among others. Available as string version (S) or with high-voltage box (H).

5,015.9 kWhRated energy
2,500 kW (2 h) / 1,250 kW (4 h)Rated power
IP55Ingress protection
4,000 mMax. altitude

Battery

Rated energy5,015.9 kWh
Rated power2,500 kW @ 0.5C / 1,250 kW @ 0.25C
Cell typeLFP 3.2 V / 314 Ah
Battery configuration1P416S × 12
Battery voltage range1,123.2–1,497.6 V DC
Nominal battery voltage1,331.2 V

Grid side

AC nominal voltage690 V AC (S version)
AC voltage range607–759 V AC
Frequency50 / 60 Hz
Current THD< 3 %
Power factor≥ 0.99 (−1 … +1)

System

CoolingLiquid cooling
Ingress protectionIP55
Operating temperature−30 to +55 °C
Relative humidity≤ 100 % RH, non-condensing
Max. altitude4,000 m
Dimensions (W × D × H)6,058 × 2,438 × 2,896 mm
Weight≤ 44,000 kg (S), ≤ 42,600 kg (H)
CommunicationEthernet

Safety

Corrosion classC4, C5 optional
Seismic ratingIEEE 693 moderate level, high level optional
Fire protectionFire alarm panel, smoke, heat and gas detectors, ventilation to NFPA 69, dry-pipe sprinklers, aerosol, deflagration venting optional

Standards and grid codes

IEC 62477-1IEC 62619IEC 61000IEC 62933IEC 63056UN 38.3CEEN 50549G99CEI 0-16VDE-AR-N 4110VDE-AR-N 4120NTS 2.1

Fire tests

Passed the CSA TS-800 large-scale fire test (February 2025): four containers in a dense layout, adjacent units stayed below 40 °C. Additional 59-hour large-scale fire test in 2025 at over 1,300 °C with no spread to neighbouring containers, witnessed by CSA Group.

Manufacturer data, 2026
Containerised utility storage

Aqua-C3.0 Ultra

More than 5 MWh in a container under 15 feet long, grid-forming capable. Silicon-carbide string inverter for high efficiency.

5,154.3 kWhRated energy
1,288 kWRated power
< 15 ftDimensions (W × D × H)
≤ 38.7 tWeight

Battery

Rated energy5,154.3 kWh
Rated power1,288 kW @ 0.25C (1,288 kVA)
Cell typeLFP 3.2 V / 587 Ah
Battery configuration392S7P
Battery voltage range1,060–1,411.2 V DC
Nominal battery voltage1,254.4 V

Grid side

AC nominal voltage690 V AC (S version)
AC voltage range607–759 V AC
Frequency50 / 60 Hz
Current THD< 3 %
Power factor≥ 0.99 (−1 … +1)

System

CoolingLiquid cooling
Ingress protectionIP55
Operating temperature−30 to +50 °C
Relative humidity≤ 100 % RH, non-condensing
Max. altitude2,000 m, 4,000 m optional
Noise75 dB(A), 65 dB(A) optional
Dimensions (W × D × H)4,400 × 2,438 × 3,050 mm (S), 3,950 × 2,438 × 3,100 mm (H)
Weight≤ 38,700 kg (S), ≤ 38,000 kg (H)
CommunicationEthernet

Safety

Corrosion classC4, C5 optional
Seismic ratingIEEE 693 moderate level, high level optional
Fire protectionFire alarm panel, smoke, heat and gas detectors, ventilation to NFPA 69, dry-pipe sprinklers, aerosol, deflagration venting optional

Standards and grid codes

IEC 61000IEC 62619UL 9540UL 9540AUN 38.3EN 50549G99VDE-AR-N 4110VDE-AR-N 4120
Manufacturer data, 2026
Containerised utility storage

Aqua-C3.0

The largest unit: 6.25 MWh per 20-foot container with 587 Ah cells. For solar parks, grid storage and large industrial sites.

6,250 kWhRated energy
3,125 kW (H)Rated power
IP55Ingress protection
4,000 mMax. altitude

Battery

Rated energy6,251 kWh (S) / 6,250 kWh (H)
Rated power1,563 kVA (S), 3,125 kW @ 0.5C (H)
Cell typeLFP 3.2 V / 587 Ah
Battery voltage range1,123.2–1,497.6 V DC
Nominal battery voltage1,331.2 V

Grid side

AC nominal voltage690 V AC (S version)
AC voltage range607–759 V AC
Frequency50 / 60 Hz
Current THD< 3 %
Power factor≥ 0.99 (−1 … +1)

System

CoolingLiquid cooling
Ingress protectionIP55
Operating temperature−30 to +50 °C
Relative humidity≤ 100 % RH, non-condensing
Max. altitude4,000 m (S); 2,000 m, 4,000 m optional (H)
Dimensions (W × D × H)6,058 × 2,438 × 2,896 mm
Weightapprox. 47,000 kg (S), ≤ 46,000 kg (H)
CommunicationEthernet, fibre optional

Safety

Corrosion classC3, C4/C5 optional
Seismic ratingIEEE 693 moderate level, high level optional
Fire protectionFire alarm panel, smoke, heat and gas detectors, ventilation to NFPA 69, dry-pipe sprinklers, aerosol, deflagration venting optional

Standards and grid codes

IEC 62477-1IEC 62619IEC 61000IEC 62933IEC 63056UN 38.3CEUL 9540AEN 50549G99CEI 0-16VDE-AR-N 4110VDE-AR-N 4120
Manufacturer data, 2026

All data as stated by the manufacturer CLOU Electronics, 2026. Subject to change. Only the technical documents accompanying our written quotation are binding. Full manufacturer datasheets and certificates are available on request.